Tahanan ( R ) dan reaktansi ( XL )
penghantar AAC tegangan 20 kV
(SPLN 64: 1985)
Luas Penampang mm2
|
Jari2mm
|
Urat
|
GMR (mm)
|
Impedansi urutan
positif (Ohm / km)
|
Impedansi urutan
Nol (Ohm / km)
|
16
|
2,2563
|
7
|
1,6380
|
1,8382 + j 0,4035
|
1,9862 + j 1,6910
|
25
|
2,8203
|
7
|
2,0475
|
1,1755 + j 0,3895
|
1,3245 + j 1,6770
|
35
|
3,3371
|
7
|
2,4227
|
0,8403 + j 0,3791
|
0,9883 + j 1,6666
|
50
|
3,9886
|
7
|
2,8957
|
0,5882 + j 0,3677
|
0,7362 + j 1,6552
|
70
|
4,7193
|
7
|
3,4262
|
0,4202 + j 0,3572
|
0,5682 + j 1,6447
|
95
|
5,4979
|
19
|
4,1674
|
0,3096 + j 0,3464
|
0,4576 + j 1,6339
|
120
|
6,1791
|
19
|
4,6837
|
0,2451 + j 0,3375
|
0,3931 + j 1,6250
|
150
|
6,9084
|
19
|
5,2365
|
0,1961 + j 0,3305
|
0,3441 + j 1,6180
|
185
|
7,6722
|
19
|
5,8155
|
0,1590 + j 0,3239
|
0,3070 + j 1,6114
|
240
|
8,7386
|
19
|
6,6238
|
0,1225 + j 0,3157
|
0,2705 + j 1,6032
|
Tahanan ( R
) dan reaktansi ( XL ) penghantar AAAC tegangan 20 kV
(SPLN 64: 1985)
(SPLN 64: 1985)
Luas Penampang (mm2)
|
Jari2mm
|
Urat
|
GMR (mm)
|
Impedansi urutan
positif (Ohm / km)
|
Impedansi urutan
Nol (Ohm / km)
|
16
|
2,2563
|
7
|
1,6380
|
2,0161 + j 0,4036
|
2,1641 + j 1,6911
|
25
|
2,8203
|
7
|
2,0475
|
1,2903 + j 0,3895
|
1,4384 + j 1,6770
|
35
|
3,3371
|
7
|
2,4227
|
0,9217 + j 0,3790
|
1,0697 + j 1,6665
|
50
|
3,9886
|
7
|
2,8957
|
0,6452 + j 0,3678
|
0,7932 + j 1,6553
|
70
|
4,7193
|
7
|
3,4262
|
0,4608 + j 03572
|
0,6088 + j 1,6447
|
95
|
5,4979
|
19
|
4,1674
|
0,3096 + j 0,3449
|
0,4876 + j 1,6324
|
120
|
6,1791
|
19
|
4,6837
|
0,2688 + j 0,3376
|
0,4168 + j 1,6324
|
150
|
6,9084
|
19
|
5,2365
|
0,2162 + j 0,3305
|
0,3631 + j 1,6180
|
185
|
7,6722
|
19
|
5,8155
|
0,1744 + j 0,3239
|
0,3224 + j 1,6114
|
240
|
8,7386
|
19
|
6,6238
|
0,1344 + j 0,3158
|
0,2824 + j 1,6034
|
Tahanan,
induktansi dan kapasitansi kabel isolasi XLPE:
N2XSEKBY/NA2XSEKBY tegangan 12 / 20 kV.
(IEC. 502)
N2XSEKBY/NA2XSEKBY tegangan 12 / 20 kV.
(IEC. 502)
∑ peng hantar
|
Penghantar
|
Tahanan maks pada
DC temp 200C
|
Tahanan pada
AC temp 900C
|
saat operasi
|
Maks
kapasitas arus temp 300C
|
Arus hub singkat
selama 1 detik
|
Teg nom. prcbn
|
|||
Luas pnmpg
|
Cu /Al
|
Induktansi (L)
|
Kapasitansi
(C)
|
dlm tanah
|
di udara
|
|||||
mm2
|
Ohm/km
|
Ohm/km
|
mH/km
|
mF/km
|
Amp
|
Amp
|
kA
|
kV/5 min
|
||
3
|
35
|
CU
|
0,5240
|
0,6680
|
0,520
|
0,131
|
164
|
173
|
5,01
|
30
|
Al
|
0,8680
|
1,1130
|
0,520
|
0,131
|
127
|
139
|
3,29
|
30
|
||
3
|
50
|
Cu
|
0,3870
|
0,4940
|
0,497
|
0,143
|
194
|
206
|
7,15
|
30
|
Al
|
0,6410
|
0,8220
|
0,497
|
0,143
|
148
|
161
|
4,70
|
30
|
||
3
|
70
|
Cu
|
0,2680
|
0,3420
|
0,467
|
0,162
|
236
|
257
|
10,01
|
30
|
Al
|
0,4430
|
0,5680
|
0,467
|
0,162
|
179
|
204
|
6,58
|
30
|
||
3
|
95
|
Cu
|
0,1930
|
0,2470
|
0,445
|
0,180
|
283
|
313
|
13,59
|
30
|
Al
|
0,3200
|
0,4110
|
0,445
|
0,180
|
214
|
242
|
8,93
|
30
|
||
3
|
120
|
Cu
|
0,1530
|
0,1960
|
0,430
|
0,195
|
322
|
360
|
17,16
|
30
|
Al
|
0,2530
|
0,3250
|
0,430
|
0,195
|
246
|
292
|
11,28
|
30
|
||
3
|
150
|
Cu
|
0,1240
|
0,1590
|
0,414
|
0,213
|
362
|
410
|
21,45
|
30
|
Al
|
0,2060
|
0,2650
|
0,414
|
0,213
|
264
|
313
|
14,10
|
30
|
||
3
|
185
|
Cu
|
0,0991
|
0,1280
|
0,404
|
0,227
|
409
|
469
|
26,46
|
30
|
Al
|
0,1640
|
0,2110
|
0,404
|
0,227
|
308
|
365
|
17,39
|
30
|
||
3
|
240
|
Cu
|
0,0754
|
0,0980
|
0,382
|
0,263
|
474
|
553
|
34,32
|
30
|
Al
|
0,1250
|
0,1620
|
0,382
|
0,273
|
358
|
425
|
22,56
|
30
|
||
3
|
300
|
Cu
|
0,0601
|
0,0790
|
0,376
|
0,276
|
533
|
629
|
42,90
|
30
|
Al
|
0,1000
|
0,1300
|
0,376
|
0,276
|
398
|
481
|
28,20
|
30
|
Impedansi
Kabel Tanah Dengan Penghantar Al
A
(mm2)
|
R
(Ω/km)
|
L
(mH/km)
|
C
(mf/km)
|
Impedansi urutan positif
(Ω /km)
|
Impedansi urutan Nol
(Ω/km)
|
150
|
0,206
|
0,33
|
0,26
|
0,206 + j 0,104
|
0,356 + j 0,312
|
240
|
0,125
|
0,31
|
0,31
|
0,125 + j0,097
|
0,275 +j0,029
|
300
|
0,100
|
0,30
|
0,34
|
0,100 + j0,094
|
0,250 + j0,282
|
terimakasih bos
BalasHapusmakasi banyak
BalasHapusterimakasih pak bos
BalasHapusTerima kasih banyak
BalasHapusKomentar ini telah dihapus oleh pengarang.
BalasHapusboleh minta file referensi yg asli? spln 64 dan IEC 502
BalasHapusterimakasih, boleh minta file asli SPLN nya
BalasHapusMaaf mau tanya kalau untuk jenis penghantar acsr 240/40 gimana ya mas?
BalasHapuskalo mau nyari data impedansi untuk Jenis penghantar ACSR 430 mm2 gmn ya mas?
BalasHapusiya bagaimana ya caranya
HapusMaaf, saya ingin menanyakan standar nilai impedans penghantar untuk saluran transmisi 150 kV jenis penghantar ACCC...
BalasHapus